Emerson Se4801T0X Redundant Wireless I\/O Card vulnerabilities
6 vulnerabilities
Known vulnerabilities in Emerson Se4801T0X Redundant Wireless I\/O Card, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.
CVE-2016-9347emersonse4801t0x_redundant_wireless_i\/o_card_firmware+1
EPSS score0.49%
An issue was discovered in Emerson SE4801T0X Redundant Wireless I/O Card V13.3, and SE4801T1X Simplex Wireless I/O Card V13.3. DeltaV Wireless I/O Cards (WIOC) running the firmware available in the DeltaV system, release v13.3, have the SSH (Secure Shell) functionality enabled unnecessarily.CVE-2022-29963emersondeltav_distributed_control_system_sq_controller_firmware+23EPSS score0.24%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. TELNET on port 18550 provides access to a root shell via hardcoded credentials. This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.CVE-2022-29962emersondeltav_distributed_control_system_sq_controller_firmware+23EPSS score0.24%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. FTP has hardcoded credentials (but may often be disabled in production). This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.CVE-2022-29965emersondeltav_distributed_control_system+24EPSS score0.18%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.CVE-2022-29964emersondeltav_distributed_control_system_sq_controller_firmware+23EPSS score0.24%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. WIOC SSH provides access to a shell as root, DeltaV, or backup via hardcoded credentials. NOTE: this is different from CVE-2014-2350.CVE-2022-30260emersondeltav_distributed_control_system_sq_controller_firmware+23EPSS score0.16%
Emerson DeltaV Distributed Control System (DCS) has insufficient verification of firmware integrity (an inadequate checksum approach, and no signature). This affects versions before 14.3 of DeltaV M-series, DeltaV S-series, DeltaV P-series, DeltaV SIS, and DeltaV CIOC/EIOC/WIOC IO cards.