Emerson vulnerabilities, page 3

83 vulnerabilities

Known vulnerabilities in Emerson products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 103 products.

8.8CVE-2020-10632emersonopenenterprise_scada_server+1
EPSS score
0.47%
Inadequate folder security permissions in Emerson OpenEnterprise versions through 3.3.4 may allow modification of important configuration files, which could cause the system to fail or behave in an unpredictable manner.
7.5CVE-2020-10636emersonopenenterprise_scada_server+1
EPSS score
0.28%
Inadequate encryption may allow the passwords for Emerson OpenEnterprise versions through 3.3.4 user accounts to be obtained.
10CVE-2020-10640emersonopenenterprise_scada_server+1
EPSS score
3.11%
Emerson OpenEnterprise versions through 3.3.4 may allow an attacker to run an arbitrary commands with system privileges or perform remote code execution via a specific communication service.
7.8CVE-2020-6971emersonvalvelink
EPSS score
0.28%
In Emerson ValveLink v12.0.264 to v13.4.118, a vulnerability in the ValveLink software may allow a local, unprivileged, trusted insider to escalate privileges due to insecure configuration parameters.
9.8CVE-2020-6970emersonopenenterprise+1
EPSS score
2.58%
A Heap-based Buffer Overflow was found in Emerson OpenEnterprise SCADA Server 2.83 (if Modbus or ROC Interfaces have been installed and are in use) and all versions of OpenEnterprise 3.1 through 3.3.3, where a specially crafted script could execute code on the OpenEnterprise Server.
7.8CVE-2020-12525emersonrosemount_transmitter_interface_software+11
EPSS score
1.36%
M&M Software fdtCONTAINER Component in versions below 3.5.20304.x and between 3.6 and 3.6.20304.x is vulnerable to deserialization of untrusted data in its project storage.
10CVE-2020-12030emersonwireless_1410_gateway_firmware+2
EPSS score
1.13%
There is a flaw in the code used to configure the internal gateway firewall when the gateway's VLAN feature is enabled. If a user enables the VLAN setting, the internal gateway firewall becomes disabled resulting in exposure of all ports used by the gateway.
7.5CVE-2014-2350emersondeltav
EPSS score
1.32%
Emerson DeltaV 10.3.1, 11.3, 11.3.1, and 12.3 uses hardcoded credentials for diagnostic services, which allows remote attackers to bypass intended access restrictions via a TCP session, as demonstrated by a session that uses the telnet program.
6.2CVE-2014-2349emersondeltav
EPSS score
0.66%
Emerson DeltaV 10.3.1, 11.3, 11.3.1, and 12.3 uses hardcoded credentials for diagnostic services, which allows remote attackers to bypass intended access restrictions via a TCP session, as demonstrated by a session that uses the telnet program.
7.3CVE-2022-2788emerson electricproficy machine edition+1
EPSS score
0.24%
Emerson Electric's Proficy Machine Edition Version 9.80 and prior is vulnerable to CWE-29 Path Traversal: '\..\Filename', also known as a ZipSlip attack, through an upload procedure which enables attackers to implant a malicious .BLZ file on the PLC. The file can transfer through the engineering station onto Windows in a way that executes the malicious code.
7.8CVE-2022-2793emerson electricproficy machine edition+1
EPSS score
0.14%
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-353 Missing Support for Integrity Check, and has no authentication or authorization of data packets after establishing a connection for the SRTP protocol.
5.9CVE-2022-2790emerson electricproficy machine edition+1
EPSS score
0.13%
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-347 Improper Verification of Cryptographic Signature, and does not properly verify compiled logic (PDT files) and data blocks data (BLD/BLK files).
7.8CVE-2022-2791emerson electricproficy machine edition+1
EPSS score
0.18%
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulnerable to CWE-434 Unrestricted Upload of File with Dangerous Type, and will upload any file written into the PLC logic folder to the connected PLC.
7.5CVE-2022-2792emerson electricproficy machine edition+1
EPSS score
0.42%
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-284 Improper Access Control, and stores project data in a directory with improper access control lists.
5.5CVE-2022-2789emerson electricproficy machine edition+1
EPSS score
0.12%
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulnerable to CWE-345 Insufficient Verification of Data Authenticity, and can display logic that is different than the compiled logic.
5.5CVE-2022-29963emersondeltav_distributed_control_system_sq_controller_firmware+23
EPSS score
0.24%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. TELNET on port 18550 provides access to a root shell via hardcoded credentials. This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.
5.5CVE-2022-29962emersondeltav_distributed_control_system_sq_controller_firmware+23
EPSS score
0.24%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. FTP has hardcoded credentials (but may often be disabled in production). This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.
5.5CVE-2022-29960emersonopenbsi
EPSS score
0.49%
Emerson OpenBSI through 2022-04-29 uses weak cryptography. It is an engineering environment for the ControlWave and Bristol Babcock line of RTUs. DES with hardcoded cryptographic keys is used for protection of certain system credentials, engineering files, and sensitive utilities.
5.5CVE-2022-29965emersondeltav_distributed_control_system+24
EPSS score
0.18%
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.
7.8CVE-2022-29957emersondeltav_distributed_control_system
EPSS score
0.22%
The Emerson DeltaV Distributed Control System (DCS) through 2022-04-29 mishandles authentication. It utilizes several proprietary protocols for a wide variety of functionality. These protocols include Firmware upgrade (18508/TCP, 18518/TCP); Plug-and-Play (18510/UDP); Hawk services (18507/UDP); Management (18519/TCP); Cold restart (18512/UDP); SIS communications (12345/TCP); and Wireless Gateway Protocol (18515/UDP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality.