Festo vulnerabilities

12 vulnerabilities

Known vulnerabilities in Festo products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 130 products.

Products

50 of 130
7.8CVE-2020-12069codesyscodesys v3 containing the cmpusermgr+64
EPSS score
0.17%
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
9.3CVE-2014-07603s-softwarecodesys_runtime_system+5
EPSS score
3.35%
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion provide an undocumented access method involving the FTP protocol, which could allow a remote attacker to execute arbitrary code or cause a denial of service (application crash) via unspecified vectors.
9.3CVE-2014-07693s-softwarecodesys_runtime_system+5
EPSS score
2.32%
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which allows remote attackers to (1) modify the configuration via a request to the debug service on port 4000 or (2) delete log entries via a request to the log service on port 4001.
10CVE-2022-30309festocontroller_cecc-x-m1_firmware+18
EPSS score
2.92%
In Festo Controller CECC-X-M1 product family in multiple versions, the http-endpoint "cecc-x-web-viewer-request-off" POST request doesn’t check for port syntax. This can result in unauthorized execution of system commands with root privileges due to improper access control command injection.
10CVE-2022-30310festocontroller_cecc-x-m1_firmware+18
EPSS score
2.69%
In Festo Controller CECC-X-M1 product family in multiple versions, the http-endpoint "cecc-x-acknerr-request" POST request doesn’t check for port syntax. This can result in unauthorized execution of system commands with root privileges due to improper access control command injection.
10CVE-2022-30308festocontroller_cecc-x-m1_firmware+18
EPSS score
2.92%
In Festo Controller CECC-X-M1 product family in multiple versions, the http-endpoint "cecc-x-web-viewer-request-on" POST request doesn’t check for port syntax. This can result in unauthorized execution of system commands with root privileges due to improper access control command injection.
10CVE-2022-30311festocontroller_cecc-x-m1_firmware+18
EPSS score
2.69%
In Festo Controller CECC-X-M1 product family in multiple versions, the http-endpoint "cecc-x-refresh-request" POST request doesn’t check for port syntax. This can result in unauthorized execution of system commands with root privileges due to improper access control command injection.
9.8CVE-2022-3270festo sebus module cpx-e-ep+153
EPSS score
1.09%
In multiple products by Festo a remote unauthenticated attacker could use functions of an undocumented protocol which could lead to a complete loss of confidentiality, integrity and availability.
7.5CVE-2022-3079festocontrol block cpx-cec-c1 (no. 567347)+3
EPSS score
0.78%
Festo control block CPX-CEC-C1 and CPX-CMXX in multiple versions allow unauthenticated, remote access to critical webpage functions which may cause a denial of service.
10CVE-2012-60693s-smart software solutionscodesys control rte+5
EPSS score
2.64%
The CoDeSys Runtime Toolkit’s file transfer functionality does not perform input validation, which allows an attacker to access files and directories outside the intended scope. This may allow an attacker to upload and download any file on the device. This could allow the attacker to affect the availability, integrity, and confidentiality of the device.
10CVE-2012-60683s-smart software solutionscodesys control rte+5
EPSS score
5.27%
The Runtime Toolkit in CODESYS Runtime System 2.3.x and 2.4.x does not require authentication, which allows remote attackers to execute commands via the command-line interface in the TCP listener service or transfer files via requests to the TCP listener service.
8.8CVE-2023-3634festomse6-c2m-5000-fb36-d-m-rg-bar-m12l4-agd+11
EPSS score
0.64%
In products of the MSE6 product-family by Festo a remote authenticated, low privileged attacker could use functions of undocumented test mode which could lead to a complete loss of confidentiality, integrity and availability.