Ge vulnerabilities

127 vulnerabilities

Known vulnerabilities in Ge products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 143 products.

Products

50 of 143
7.5CVE-2018-19003geex2100e_firmware+2
EPSS score
2.56%
GE Mark VIe, EX2100e, EX2100e_Reg, and LS2100e Versions 03.03.28C to 05.02.04C, EX2100e All versions prior to v04.09.00C, EX2100e_Reg All versions prior to v04.09.00C, and LS2100e All versions prior to v04.09.00C The affected versions of the application have a path traversal vulnerability that fails to restrict the ability of an attacker to gain access to restricted information.
4.8CVE-2018-17925geifix
EPSS score
0.30%
Multiple instances of this vulnerability (Unsafe ActiveX Control Marked Safe For Scripting) have been identified in the third-party ActiveX object provided to GE iFIX versions 2.0 - 5.8 by Gigasoft. Only the independent use of the Gigasoft charting package outside the iFIX product may expose users to the reported vulnerability. The reported method shown to impact Internet Explorer is not exposed in the iFIX product, nor is the core functionality of the iFIX product known to be impacted.
10CVE-2018-5473ged60_line_distance_relay_firmware
EPSS score
5.89%
An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote attacker to execute arbitrary code on the device.
9.8CVE-2018-5475ged60_line_distance_relay_firmware
EPSS score
3.79%
A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.
8.1CVE-2018-10615gemds_pulsenet+1
EPSS score
2.54%
Directory traversal may lead to files being exfiltrated or deleted on the GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior host platform.
9.8CVE-2018-10611gemds_pulsenet+1
EPSS score
4.93%
Java remote method invocation (RMI) input port in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior may be exploited to allow unauthenticated users to launch applications and support remote code execution through web services.
7.5CVE-2018-10613gemds_pulsenet+1
EPSS score
17.84%
Multiple variants of XML External Entity (XXE) attacks may be used to exfiltrate data from the host Windows platform in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior.
9.1CVE-2018-15362gecimplicity
EPSS score
2.69%
XXE in GE Proficy Cimplicity GDS versions 9.0 R2, 9.5, 10.0
7.8CVE-2018-8867gepacsystems_cpu320_firmware+7
EPSS score
3.38%
In GE PACSystems RX3i CPE305/310 version 9.20 and prior, RX3i CPE330 version 9.21 and prior, RX3i CPE 400 version 9.30 and prior, PACSystems RSTi-EP CPE 100 all versions, and PACSystems CPU320/CRU320 RXi all versions, the device does not properly validate input, which could allow a remote attacker to send specially crafted packets causing the device to become unavailable.
9.3CVE-2013-2785geintelligent_platforms_proficy_hmi\/scada_cimplicity+1
EPSS score
3.77%
Multiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, 8.1 before SIM 25, and 8.2 before SIM 19, and Proficy Process Systems with CIMPLICITY, allow remote attackers to execute arbitrary code via crafted data in packets to TCP port 10212, aka ZDI-CAN-1621 and ZDI-CAN-1624.
7.1CVE-2013-2811catapultsoftwarecatapult_dnp3_i\/o_driver+3
EPSS score
1.85%
The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet.
4.7CVE-2013-2823catapultsoftwarecatapult_dnp3_i\/o_driver+3
EPSS score
0.76%
The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line.
5CVE-2013-0652geintelligent_platforms_proficy_real-time_information_portal
EPSS score
1.96%
GE Intelligent Platforms Proficy Real-Time Information Portal does not restrict access to methods of an unspecified Java class, which allows remote attackers to obtain a username listing via an RMI call.
4.3CVE-2013-0653geintelligent_platforms_proficy_hmi\/scada_cimplicity+2
EPSS score
19.11%
Directory traversal vulnerability in substitute.bcl in the WebView CimWeb subsystem in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to read arbitrary files via a crafted packet.
5CVE-2013-0651geintelligent_platforms_proficy_real-time_information_portal
EPSS score
1.31%
The Portal installation process in GE Intelligent Platforms Proficy Real-Time Information Portal stores sensitive information under the web root with insufficient access control, which allows remote attackers to read configuration files, and discover data-source credentials, via a direct request.
9.3CVE-2013-0654geintelligent_platforms_proficy_hmi\/scada_cimplicity+2
EPSS score
3.06%
CimWebServer in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary commands or cause a denial of service (daemon crash) via a crafted packet.
7.5CVE-2021-31477gereason_rpv311_firmware
EPSS score
2.64%
This vulnerability allows remote attackers to execute arbitrary code on affected installations of GE Reason RPV311 14A03. Authentication is not required to exploit this vulnerability. The specific flaw exists within the firmware and filesystem of the device. The firmware and filesystem contain hard-coded default credentials. An attacker can leverage this vulnerability to execute code in the context of the download user. Was ZDI-CAN-11852.
7.8CVE-2021-27452gemu320e_firmware
EPSS score
0.27%
The software contains a hard-coded password that could allow an attacker to take control of the merging unit using these hard-coded credentials on the MU320E (all firmware versions prior to v04A00.1).
8.4CVE-2021-27430geur_bootloader_binary
EPSS score
0.25%
GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR.
7.8CVE-2021-27450gemu320e_firmware
EPSS score
0.20%
SSH server configuration file does not implement some best practices. This could lead to a weakening of the SSH protocol strength, which could lead to additional misconfiguration or be leveraged as part of a larger attack on the MU320E (all firmware versions prior to v04A00.1).