ICS CERT vulnerabilities

92 vulnerabilities

Known vulnerabilities in ICS CERT products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 42 products.

Products

42
6.5CVE-2018-19014ics-certdräger infinity delta
EPSS score
0.79%
Drager Infinity Delta, Infinity Delta, all versions, Delta XL, all versions, Kappa, all version, and Infinity Explorer C700, all versions. Log files are accessible over an unauthenticated network connection. By accessing the log files, an attacker is able to gain insights about internals of the patient monitor, the location of the monitor, and wired network configuration.
4.3CVE-2018-19004ics-certlcds laquis scada+1
EPSS score
3.73%
LCDS Laquis SCADA prior to version 4.1.0.4150 allows out of bounds read when opening a specially crafted project file, which may allow data exfiltration.
8.8CVE-2018-19017ics-certcx-supervisor+1
EPSS score
2.40%
Several use after free vulnerabilities have been identified in CX-Supervisor (Versions 3.42 and prior). When processing project files, the application fails to check if it is referencing freed memory. An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application.
7.8CVE-2018-19008abbcp400pb_firmware+1
EPSS score
1.57%
The TextEditor 2.0 in ABB CP400 Panel Builder versions 2.0.7.05 and earlier contain a vulnerability in the file parser of the Text Editor wherein the application doesn't properly prevent the insertion of specially crafted files which could allow arbitrary code execution.
5CVE-2018-19020ics-certcx-supervisor+1
EPSS score
0.83%
When CX-Supervisor (Versions 3.42 and prior) processes project files and tampers with the value of an offset, an attacker can force the application to read a value outside of an array.
7.8CVE-2018-19012ics-certdräger infinity delta
EPSS score
0.39%
Drager Infinity Delta, Infinity Delta, all versions, Delta XL, all versions, Kappa, all version, and Infinity Explorer C700, all versions. Via a specific dialog it is possible to break out of the kiosk mode and reach the underlying operating system. By breaking out of the kiosk mode, an attacker is able to take control of the operating system.
7.3CVE-2018-19015ics-certcx-supervisor+1
EPSS score
1.48%
An attacker could inject commands to launch programs and create, write, and read files on CX-Supervisor (Versions 3.42 and prior) through a specially crafted project file. An attacker could exploit this to execute code under the privileges of the application.
6.5CVE-2018-19010ics-certdräger infinity delta
EPSS score
0.77%
Drager Infinity Delta, Infinity Delta, all versions, Delta XL, all versions, Kappa, all version, and Infinity Explorer C700, all versions. A malformed network packet may cause the monitor to reboot. By repeatedly sending the malformed network packet, an attacker may be able to disrupt patient monitoring by causing the monitor to repeatedly reboot until it falls back to default configuration and loses network connectivity.
7.3CVE-2018-19019ics-certcx-supervisor+1
EPSS score
1.50%
A type confusion vulnerability exists when processing project files in CX-Supervisor (Versions 3.42 and prior). An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application.
7.3CVE-2018-19018ics-certcx-supervisor+1
EPSS score
1.16%
An access of uninitialized pointer vulnerability in CX-Supervisor (Versions 3.42 and prior) could lead to type confusion when processing project files. An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application.
5CVE-2018-19013ics-certcx-supervisor+1
EPSS score
0.75%
An attacker could inject commands to delete files and/or delete the contents of a file on CX-Supervisor (Versions 3.42 and prior) through a specially crafted project file.
5.3CVE-2018-19000ics-certlcds laquis scada+1
EPSS score
8.79%
LCDS Laquis SCADA prior to version 4.1.0.4150 allows an authentication bypass, which may allow an attacker access to sensitive data.
8.8CVE-2018-19011ics-certcx-supervisor+1
EPSS score
2.42%
CX-Supervisor (Versions 3.42 and prior) can execute code that has been injected into a project file. An attacker could exploit this to execute code under the privileges of the application.
7.5CVE-2018-14785ics-certnetcomm wireless g lte light industrial m2m router (nwl-25) with firmware 2.0.29.11 and prior.+1
EPSS score
2.13%
NetComm Wireless G LTE Light Industrial M2M Router (NWL-25) with firmware 2.0.29.11 and prior. The directory of the device is listed openly without authentication.
7.5CVE-2018-14782ics-certnetcomm wireless g lte light industrial m2m router (nwl-25) with firmware 2.0.29.11 and prior.+1
EPSS score
1.60%
NetComm Wireless G LTE Light Industrial M2M Router (NWL-25) with firmware 2.0.29.11 and prior. The device allows access to configuration files and profiles without authenticating the user.
8.8CVE-2018-14793emersondeltav+1
EPSS score
1.03%
DeltaV Versions 11.3.1, 12.3.1, 13.3.0, 13.3.1, and R5 is vulnerable to a buffer overflow exploit through an open communication port to allow arbitrary code execution.
9.8CVE-2018-14805hitachienergyesoms+1
EPSS score
4.81%
ABB eSOMS version 6.0.2 may allow unauthorized access to the system when LDAP is set to allow anonymous authentication, and specific key values within the eSOMS web.config file are present. Both conditions are required to exploit this vulnerability.
8.8CVE-2018-14795emersondeltav+1
EPSS score
2.19%
DeltaV Versions 11.3.1, 12.3.1, 13.3.0, 13.3.1, and R5 is vulnerable due to improper path validation which may allow an attacker to replace executable files.
8.8CVE-2018-14783ics-certnetcomm wireless g lte light industrial m2m router (nwl-25) with firmware 2.0.29.11 and prior.+1
EPSS score
0.66%
NetComm Wireless G LTE Light Industrial M2M Router (NWL-25) with firmware 2.0.29.11 and prior. A cross-site request forgery condition can occur, allowing an attacker to change passwords of the device remotely.
6.1CVE-2018-14784ics-certnetcomm wireless g lte light industrial m2m router (nwl-25) with firmware 2.0.29.11 and prior.+1
EPSS score
0.98%
NetComm Wireless G LTE Light Industrial M2M Router (NWL-25) with firmware 2.0.29.11 and prior. The device is vulnerable to several cross-site scripting attacks, allowing a remote attacker to run arbitrary code on the device.