Rockwell Automation vulnerabilities

312 vulnerabilities

Known vulnerabilities in Rockwell Automation products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 228 products.

Products

50 of 228
8.7CVE-2026-12656rockwell automation1732e armorblock® i/o
EPSS score
0.25%
A denial-of-service security issue exists in the affected product and version. The security issue stems from improper handling of network storm traffic, which can interrupt communication, cause device faults, and affect open TCP and UDP ports. A power cycle is required to recover the device to its normal state.
8.8CVE-2026-12655rockwell automation1732e armorblock® i/o
EPSS score
0.27%
A security issue exists within 1732E ArmorBlock® I/O, where an unauthenticated attacker can change the device's webserver password without valid credentials. This could result in admin account takeover or unauthorized modification of device configuration.
9.8CVE-2018-14829rockwell automationrslinx classic®+1
EPSS score
16.09%
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote threat actor to intentionally send a malformed CIP packet to Port 44818, causing the software application to stop responding and crash. This vulnerability also has the potential to exploit a buffer overflow condition, which may allow the threat actor to remotely execute arbitrary code.
7.5CVE-2018-14821rockwell automationrslinx classic®+1
EPSS score
4.50%
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote, unauthenticated threat actor to intentionally send a malformed CIP packet to Port 44818, causing the RSLinx Classic application to terminate. The user will need to manually restart the software to regain functionality.
7.5CVE-2018-14827rockwell automationrslinx classic®+1
EPSS score
3.76%
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. A remote, unauthenticated threat actor may intentionally send specially crafted Ethernet/IP packets to Port 44818, causing the software application to stop responding and crash. The user must restart the software to regain functionality.
7.8CVE-2013-2806rockwell automationrslinx enterprise software+1
EPSS score
3.85%
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
7.8CVE-2013-2807rockwell automationrslinx enterprise software+1
EPSS score
3.85%
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
7.8CVE-2013-2805rockwell automationrslinx enterprise software+1
EPSS score
3.85%
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
10CVE-2021-27470rockwell automationfactorytalk® assetcentre+1
EPSS score
3.83%
A deserialization vulnerability exists in how the LogService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre.
10CVE-2021-27468rockwell automationfactorytalk® assetcentre+1
EPSS score
3.49%
The AosService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier exposes functions lacking proper authentication. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary SQL statements.
8.6CVE-2021-27471rockwell automationconnected components workbench+1
EPSS score
2.86%
The parsing mechanism that processes certain file types does not provide input sanitization for file paths. This may allow an attacker to craft malicious files that, when opened by Rockwell Automation Connected Components Workbench v12.00.00 and prior, can traverse the file system. If successfully exploited, an attacker could overwrite existing files and create additional files with the same permissions of the Connected Components Workbench software. User interaction is required for this exploit to be successful.
8.6CVE-2021-27475rockwell automationconnected components workbench+1
EPSS score
2.99%
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not limit the objects that can be deserialized. This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited.
10CVE-2021-27466rockwell automationfactorytalk® assetcentre+1
EPSS score
3.89%
A deserialization vulnerability exists in how the ArchiveService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre.
8.2CVE-2021-27473rockwell automationconnected components workbench+1
EPSS score
0.78%
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not sanitize paths specified within the .ccwarc archive file during extraction. This type of vulnerability is also commonly referred to as a Zip Slip. A local, authenticated attacker can create a malicious .ccwarc archive file that, when opened by Connected Components Workbench, will allow the attacker to gain the privileges of the software. If the software is running at SYSTEM level, the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.
10CVE-2021-27460rockwell automationfactorytalk® assetcentre+1
EPSS score
3.19%
Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier components contain .NET remoting endpoints that deserialize untrusted data without sufficiently verifying that the resulting data will be valid. This vulnerability may allow a remote, unauthenticated attacker to gain full access to the FactoryTalk AssetCentre main server and all agent machines.
10CVE-2021-27474rockwell automationfactorytalk® assetcentre+1
EPSS score
1.61%
Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier does not properly restrict all functions relating to IIS remoting services. This vulnerability may allow a remote, unauthenticated attacker to modify sensitive data in FactoryTalk AssetCentre.
10CVE-2021-27462rockwell automationfactorytalk® assetcentre+1
EPSS score
3.83%
A deserialization vulnerability exists in how the AosService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre.
10CVE-2021-27472rockwell automationfactorytalk® assetcentre+1
EPSS score
5.66%
A vulnerability exists in the RunSearch function of SearchService service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier, which may allow for the execution of remote unauthenticated arbitrary SQL statements.
10CVE-2021-27476rockwell automationfactorytalk® assetcentre+1
EPSS score
4.11%
A vulnerability exists in the SaveConfigFile function of the RACompare Service, which may allow for OS command injection. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier.
10CVE-2021-27464rockwell automationfactorytalk® assetcentre+1
EPSS score
3.48%
The ArchiveService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier exposes functions lacking proper authentication. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary SQL statements.