Rockwellautomation Factorytalk View vulnerabilities

15 vulnerabilities

Known vulnerabilities in Rockwellautomation Factorytalk View, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

9.1CVE-2025-9064rockwell automationfactorytalk view machine edition+1
EPSS score
0.61%
A path traversal security issue exists within FactoryTalk View Machine Edition, allowing unauthenticated attackers on the same network as the device to delete any file within the panels operating system. Exploitation of this vulnerability is dependent on the knowledge of filenames to be deleted.
9.8CVE-2025-9063rockwell automationpanelview plus 7 performance series b+1
EPSS score
0.39%
An authentication bypass security issue exists within FactoryTalk View Machine Edition Web Browser ActiveX control. Exploitation of this vulnerability allows unauthorized access to the PanelView Plus 7 Series B, including access to the file system, retrieval of diagnostic information, event logs, and more.
5.5CVE-2020-14480rockwell automationfactorytalk® view se+1
EPSS score
0.27%
Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials.
7.8CVE-2020-14481rockwell automationfactorytalk® view se+1
EPSS score
0.16%
The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE.
9CVE-2020-12029rockwell automationfactorytalk® view se+1
EPSS score
46.97%
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
5.3CVE-2024-21914rockwell automationfactorytalk® view me+1
EPSS score
0.66%
A vulnerability exists in the affected product that allows a malicious user to restart the Rockwell Automation PanelView™ Plus 7 terminal remotely without security protections. If the vulnerability is exploited, it could lead to the loss of view or control of the PanelView™ product.
9.8CVE-2024-4609rockwell automationfactorytalk® view se+1
EPSS score
0.65%
A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime.
8.8CVE-2024-37369rockwell automationfactorytalk® view se+1
EPSS score
0.33%
A privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.
8.2CVE-2024-37367rockwell automationfactorytalk® view se+1
EPSS score
0.50%
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.
8.2CVE-2024-37368rockwell automationfactorytalk® view se+1
EPSS score
0.50%
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.
7.8CVE-2024-37365rockwell automationfactorytalk view machine edition+1
EPSS score
0.22%
A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.
8.8CVE-2024-7513rockwell automationfactorytalk® view site edition+1
EPSS score
1.66%
CVE-2024-7513 IMPACT A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.
9.8CVE-2024-45824rockwell automationfactorytalk® view site edition+1
EPSS score
1.28%
CVE-2024-45824 IMPACT A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with Path Traversal, Command Injection, and XSS Vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue.
9.8CVE-2023-2071rockwell automationfa+1
EPSS score
17.27%
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
7.5CVE-2023-46289rockwell automationfactorytalk® view site edition+1
EPSS score
0.90%
Rockwell Automation FactoryTalk View Site Edition insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.