Rockwellautomation Guardlogix 5580 vulnerabilities

11 vulnerabilities

Known vulnerabilities in Rockwellautomation Guardlogix 5580, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

8.6CVE-2020-6998rockwell automationarmor compact guardlogix 5370 controllers+15
EPSS score
3.16%
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
8.6CVE-2022-1797rockwell automationcompact guardlogix 5370 controllers+17
EPSS score
2.16%
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
8.6CVE-2022-3752rockwell automationcompact guardlogix 5380+9
EPSS score
1.30%
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
8.7CVE-2024-40619rockwell automationcontrollogix 5580+3
EPSS score
0.58%
CVE-2024-40619 IMPACT A denial-of-service vulnerability exists in the affected products. The vulnerability occurs when a malformed CIP packet is sent over the network to the device and results in a major nonrecoverable fault causing a denial-of-service.
8.7CVE-2024-7515rockwell automationcompact guardlogix 5380 (5069 – l3zs2)+10
EPSS score
0.52%
CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.
8.7CVE-2024-7507rockwell automationcompact guardlogix 5380 (5069- l3zs2)+10
EPSS score
0.50%
CVE-2024-7507 IMPACT A denial-of-service vulnerability exists in the affected products. This vulnerability occurs when a malformed PCCC message is received, causing a fault in the controller.
8.3CVE-2024-5659rockwell automation1756-en4+11
EPSS score
0.31%
Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.
8.7CVE-2024-6207rockwell automationcompact guardlogix 5380 sil 2+15
EPSS score
0.55%
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.
8.7CVE-2024-6077rockwell automation1756-en4+15
EPSS score
0.56%
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.
8.7CVE-2024-8626rockwell automation1756-en4tr+10
EPSS score
0.52%
Due to a memory leak, a denial-of-service vulnerability exists in the Rockwell Automation affected products. A malicious actor could exploit this vulnerability by performing multiple actions on certain web pages of the product causing the affected products to become fully unavailable and require a power cycle to recover.
8.6CVE-2024-3493rockwell automation1756-en4tr+11
EPSS score
0.64%
A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices.