Schneider Electric Ecostruxure Control Expert vulnerabilities

18 vulnerabilities

Known vulnerabilities in Schneider Electric Ecostruxure Control Expert, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

7.1CVE-2021-22780schneider-electricecostruxure_control_expert
EPSS score
0.22%
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file.
9.3CVE-2021-22797schneider electricecostruxure control expert+5
EPSS score
26.10%
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal) vulnerability exists that could cause malicious script to be deployed in an unauthorized location and may result in code execution on the engineering workstation when a malicious project file is loaded in the engineering software. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior, including former Unity Pro), EcoStruxure Process Expert (2020 and prior, including former HDCS), SCADAPack RemoteConnect for x70 (All versions)
5.5CVE-2021-22781schneider-electricecostruxure_control_expert
EPSS score
0.24%
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file.
5.5CVE-2021-22782schneider-electricecostruxure_control_expert
EPSS score
0.11%
Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file.
7.1CVE-2021-22778schneider-electricecostruxure_control_expert
EPSS score
0.22%
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file.
9.1CVE-2021-22779schneider-electricecostruxure_control_expert
EPSS score
1.05%
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
9.8CVE-2020-7475schneider-electricecostruxure_control_expert+2
EPSS score
1.58%
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), reflective DLL, vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20), Modicon M580 (all versions prior to V3.10), which, if exploited, could allow attackers to transfer malicious code to the controller.
9.8CVE-2022-26507attxmill+3
EPSS score
2.42%
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer
5.5CVE-2022-37302schneider electricecostruxure control expert+1
EPSS score
0.20%
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a crash of the Control Expert software when an incorrect project file is opened. Affected Products: EcoStruxure Control Expert(V15.1 HF001 and prior).
9.8CVE-2022-37300schneider electricecostruxure control expert+39
EPSS score
0.77%
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
5.9CVE-2022-24322schneider electricecostruxure control expert+1
EPSS score
0.64%
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior)
5.9CVE-2022-24323schneider electricecostruxure control expert+3
EPSS score
0.86%
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Process Expert (V2021 and prior), EcoStruxure Control Expert (V15.0 SP1 and prior)
7.5CVE-2019-6855schneider-electricecostruxure_control_expert+21
EPSS score
0.95%
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
5.5CVE-2023-1548schneider electricecostruxure control expert+1
EPSS score
0.15%
A CWE-269: Improper Privilege Management vulnerability exists that could cause a local user to perform a denial of service through the console server service that is part of EcoStruxure Control Expert. Affected Products: EcoStruxure Control Expert (V15.1 and above)
7.1CVE-2023-27975schneider electricecostruxure control expert+3
EPSS score
0.15%
CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation.
8.8CVE-2023-27976schneider electricecostruxure control expert+1
EPSS score
0.84%
A CWE-668: Exposure of Resource to Wrong Sphere vulnerability exists that could cause remote code execution when a valid user visits a malicious link provided through the web endpoints. Affected Products: EcoStruxure Control Expert (V15.1 and above)
8.1CVE-2023-6408schneider electricecostruxure control expert+44
EPSS score
0.32%
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.
7.7CVE-2023-6409schneider electricecostruxure control expert+3
EPSS score
0.23%
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert.