Schneider Electric Modicon M241 vulnerabilities

6 vulnerabilities

Known vulnerabilities in Schneider Electric Modicon M241, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

7.8CVE-2021-22699schneider-electricmodicon_m241_firmware+1
EPSS score
0.98%
Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior to V5.1.9.1 that could cause denial of service when specific crafted requests are sent to the controller over HTTP.
6.9CVE-2025-13901schneider electricmodicon m241/m251+4
EPSS score
0.47%
CWE-404 Improper Resource Shutdown or Release vulnerability exists that could cause partial Denial of Service on Machine Expert protocol when an unauthenticated attacker sends malicious payload to occupy active communication channels.
5.4CVE-2025-13902schneider electricmodicon controllers m241/m251+5
EPSS score
0.23%
CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause condition where authenticated attackers can have a victim’s browser run arbitrary JavaScript when the victim hovers over a maliciously crafted element on a web server containing the injected payload.
6.5CVE-2017-6030schneider electricmodicon m221+5
EPSS score
2.14%
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
9.8CVE-2017-6028schneider-electricmodicon_m241_firmware+1
EPSS score
2.25%
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
9.1CVE-2017-6026schneider-electricmodicon_m241_firmware+1
EPSS score
31.82%
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised.