Schneider Electric Modicon M340 Bmxp3420102 vulnerabilities, page 2

24 vulnerabilities

Known vulnerabilities in Schneider Electric Modicon M340 Bmxp3420102, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

9.8CVE-2022-45788schneider electricecostruxure control expert+61
EPSS score
1.17%
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
7.8CVE-2017-6017schneider-electricbmxnoc0401_firmware+14
EPSS score
4.81%
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
7.5CVE-2019-6855schneider-electricecostruxure_control_expert+21
EPSS score
0.95%
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
8.1CVE-2023-6408schneider electricecostruxure control expert+44
EPSS score
0.32%
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.