Siemens Scalance X200 4P Irt vulnerabilities

13 vulnerabilities

Known vulnerabilities in Siemens Scalance X200 4P Irt, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

8.3CVE-2013-5709siemensscalance_x-200_firmware+8
EPSS score
2.99%
The authentication implementation in the web server on Siemens SCALANCE X-200 switches with firmware before 5.0.0 does not use a sufficient source of entropy for generating values of random numbers, which makes it easier for remote attackers to hijack sessions by predicting a value.
7.5CVE-2013-3634siemensscalance_x200-4p_irt_firmware+6
EPSS score
1.44%
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials.
8CVE-2013-3633siemensscalance_x200-4p_irt_firmware+6
EPSS score
1.20%
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account.
9.8CVE-2021-25669siemensscalance_x200-4p_irt_firmware+34
EPSS score
2.13%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < 5.5.1), SCALANCE X201-3P IRT (All versions < 5.5.1), SCALANCE X201-3P IRT PRO (All versions < 5.5.1), SCALANCE X202-2 IRT (All versions < 5.5.1), SCALANCE X202-2P IRT (incl. SIPLUS NET variant) (All versions < 5.5.1), SCALANCE X202-2P IRT PRO (All versions < 5.5.1), SCALANCE X204 IRT (All versions < 5.5.1), SCALANCE X204 IRT PRO (All versions < 5.5.1), SCALANCE X204-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X204-2FM (All versions < V5.2.5), SCALANCE X204-2LD (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X204-2LD TS (All versions < V5.2.5), SCALANCE X204-2TS (All versions < V5.2.5), SCALANCE X206-1 (All versions < V5.2.5), SCALANCE X206-1LD (All versions < V5.2.5), SCALANCE X208 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X208PRO (All versions < V5.2.5), SCALANCE X212-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X212-2LD (All versions < V5.2.5), SCALANCE X216 (All versions < V5.2.5), SCALANCE X224 (All versions < V5.2.5), SCALANCE XF201-3P IRT (All versions < 5.5.1), SCALANCE XF202-2P IRT (All versions < 5.5.1), SCALANCE XF204 (All versions < V5.2.5), SCALANCE XF204 IRT (All versions < 5.5.1), SCALANCE XF204-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE XF204-2BA IRT (All versions < 5.5.1), SCALANCE XF206-1 (All versions < V5.2.5), SCALANCE XF208 (All versions < V5.2.5). Incorrect processing of POST requests in the web server may write out of bounds in stack. An attacker might leverage this to denial-of-service of the device or remote code execution.
9.8CVE-2021-25668siemensscalance_x200-4p_irt_firmware+34
EPSS score
1.57%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < 5.5.1), SCALANCE X201-3P IRT (All versions < 5.5.1), SCALANCE X201-3P IRT PRO (All versions < 5.5.1), SCALANCE X202-2 IRT (All versions < 5.5.1), SCALANCE X202-2P IRT (incl. SIPLUS NET variant) (All versions < 5.5.1), SCALANCE X202-2P IRT PRO (All versions < 5.5.1), SCALANCE X204 IRT (All versions < 5.5.1), SCALANCE X204 IRT PRO (All versions < 5.5.1), SCALANCE X204-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X204-2FM (All versions < V5.2.5), SCALANCE X204-2LD (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X204-2LD TS (All versions < V5.2.5), SCALANCE X204-2TS (All versions < V5.2.5), SCALANCE X206-1 (All versions < V5.2.5), SCALANCE X206-1LD (All versions < V5.2.5), SCALANCE X208 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X208PRO (All versions < V5.2.5), SCALANCE X212-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE X212-2LD (All versions < V5.2.5), SCALANCE X216 (All versions < V5.2.5), SCALANCE X224 (All versions < V5.2.5), SCALANCE XF201-3P IRT (All versions < 5.5.1), SCALANCE XF202-2P IRT (All versions < 5.5.1), SCALANCE XF204 (All versions < V5.2.5), SCALANCE XF204 IRT (All versions < 5.5.1), SCALANCE XF204-2 (incl. SIPLUS NET variant) (All versions < V5.2.5), SCALANCE XF204-2BA IRT (All versions < 5.5.1), SCALANCE XF206-1 (All versions < V5.2.5), SCALANCE XF208 (All versions < V5.2.5). Incorrect processing of POST requests in the webserver may result in write out of bounds in heap. An attacker might leverage this to cause denial-of-service on the device and potentially remotely execute code.
8.7CVE-2020-28400siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+309
EPSS score
1.86%
Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial of service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.
6.1CVE-2022-40631siemensscalance_x200-4p_irt_firmware+29
EPSS score
0.52%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.0), SCALANCE X201-3P IRT (All versions < V5.5.0), SCALANCE X201-3P IRT PRO (All versions < V5.5.0), SCALANCE X202-2IRT (All versions < V5.5.0), SCALANCE X202-2P IRT (All versions < V5.5.0), SCALANCE X202-2P IRT PRO (All versions < V5.5.0), SCALANCE X204-2 (All versions < V5.2.5), SCALANCE X204-2FM (All versions < V5.2.5), SCALANCE X204-2LD (All versions < V5.2.5), SCALANCE X204-2LD TS (All versions < V5.2.5), SCALANCE X204-2TS (All versions < V5.2.5), SCALANCE X204IRT (All versions < V5.5.0), SCALANCE X204IRT PRO (All versions < V5.5.0), SCALANCE X206-1 (All versions < V5.2.5), SCALANCE X206-1LD (All versions < V5.2.5), SCALANCE X208 (All versions < V5.2.5), SCALANCE X208PRO (All versions < V5.2.5), SCALANCE X212-2 (All versions < V5.2.5), SCALANCE X212-2LD (All versions < V5.2.5), SCALANCE X216 (All versions < V5.2.5), SCALANCE X224 (All versions < V5.2.5), SCALANCE XF201-3P IRT (All versions < V5.5.0), SCALANCE XF202-2P IRT (All versions < V5.5.0), SCALANCE XF204 (All versions < V5.2.5), SCALANCE XF204-2 (All versions < V5.2.5), SCALANCE XF204-2BA IRT (All versions < V5.5.0), SCALANCE XF204IRT (All versions < V5.5.0), SCALANCE XF206-1 (All versions < V5.2.5), SCALANCE XF208 (All versions < V5.2.5), SIPLUS NET SCALANCE X202-2P IRT (All versions < V5.5.0). There is a cross-site scripting vulnerability on the affected devices, that if used by a threat actor, it could result in session hijacking.
9.6CVE-2022-26649siemensscalance_x200-4p_irt_firmware+29
EPSS score
1.36%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT PRO (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2P IRT (All versions < V5.5.2), SCALANCE X202-2P IRT PRO (All versions < V5.5.2), SCALANCE X204-2 (All versions < V5.2.6), SCALANCE X204-2FM (All versions < V5.2.6), SCALANCE X204-2LD (All versions < V5.2.6), SCALANCE X204-2LD TS (All versions < V5.2.6), SCALANCE X204-2TS (All versions < V5.2.6), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT PRO (All versions < V5.5.2), SCALANCE X206-1 (All versions < V5.2.6), SCALANCE X206-1LD (All versions < V5.2.6), SCALANCE X208 (All versions < V5.2.6), SCALANCE X208PRO (All versions < V5.2.6), SCALANCE X212-2 (All versions < V5.2.6), SCALANCE X212-2LD (All versions < V5.2.6), SCALANCE X216 (All versions < V5.2.6), SCALANCE X224 (All versions < V5.2.6), SCALANCE XF201-3P IRT (All versions < V5.5.2), SCALANCE XF202-2P IRT (All versions < V5.5.2), SCALANCE XF204 (All versions < V5.2.6), SCALANCE XF204-2 (All versions < V5.2.6), SCALANCE XF204-2BA IRT (All versions < V5.5.2), SCALANCE XF204IRT (All versions < V5.5.2), SCALANCE XF206-1 (All versions < V5.2.6), SCALANCE XF208 (All versions < V5.2.6). Affected devices do not properly validate the URI of incoming HTTP GET requests. This could allow an unauthenticated remote attacker to crash affected devices.
8.2CVE-2022-26648siemensscalance_x200-4p_irt_firmware+29
EPSS score
0.97%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT PRO (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2P IRT (All versions < V5.5.2), SCALANCE X202-2P IRT PRO (All versions < V5.5.2), SCALANCE X204-2 (All versions < V5.2.6), SCALANCE X204-2FM (All versions < V5.2.6), SCALANCE X204-2LD (All versions < V5.2.6), SCALANCE X204-2LD TS (All versions < V5.2.6), SCALANCE X204-2TS (All versions < V5.2.6), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT PRO (All versions < V5.5.2), SCALANCE X206-1 (All versions < V5.2.6), SCALANCE X206-1LD (All versions < V5.2.6), SCALANCE X208 (All versions < V5.2.6), SCALANCE X208PRO (All versions < V5.2.6), SCALANCE X212-2 (All versions < V5.2.6), SCALANCE X212-2LD (All versions < V5.2.6), SCALANCE X216 (All versions < V5.2.6), SCALANCE X224 (All versions < V5.2.6), SCALANCE XF201-3P IRT (All versions < V5.5.2), SCALANCE XF202-2P IRT (All versions < V5.5.2), SCALANCE XF204 (All versions < V5.2.6), SCALANCE XF204-2 (All versions < V5.2.6), SCALANCE XF204-2BA IRT (All versions < V5.5.2), SCALANCE XF204IRT (All versions < V5.5.2), SCALANCE XF206-1 (All versions < V5.2.6), SCALANCE XF208 (All versions < V5.2.6). Affected devices do not properly validate the GET parameter XNo of incoming HTTP requests. This could allow an unauthenticated remote attacker to crash affected devices.
8.8CVE-2022-26647siemensscalance_x200-4p_irt_firmware+29
EPSS score
1.17%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT PRO (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2P IRT (All versions < V5.5.2), SCALANCE X202-2P IRT PRO (All versions < V5.5.2), SCALANCE X204-2 (All versions < V5.2.6), SCALANCE X204-2FM (All versions < V5.2.6), SCALANCE X204-2LD (All versions < V5.2.6), SCALANCE X204-2LD TS (All versions < V5.2.6), SCALANCE X204-2TS (All versions < V5.2.6), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT PRO (All versions < V5.5.2), SCALANCE X206-1 (All versions < V5.2.6), SCALANCE X206-1LD (All versions < V5.2.6), SCALANCE X208 (All versions < V5.2.6), SCALANCE X208PRO (All versions < V5.2.6), SCALANCE X212-2 (All versions < V5.2.6), SCALANCE X212-2LD (All versions < V5.2.6), SCALANCE X216 (All versions < V5.2.6), SCALANCE X224 (All versions < V5.2.6), SCALANCE XF201-3P IRT (All versions < V5.5.2), SCALANCE XF202-2P IRT (All versions < V5.5.2), SCALANCE XF204 (All versions < V5.2.6), SCALANCE XF204-2 (All versions < V5.2.6), SCALANCE XF204-2BA IRT (All versions < V5.5.2), SCALANCE XF204IRT (All versions < V5.5.2), SCALANCE XF206-1 (All versions < V5.2.6), SCALANCE XF208 (All versions < V5.2.6). The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force session ids and hijack existing sessions.
7.8CVE-2019-13946siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+190
EPSS score
1.46%
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack. The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device.
7.5CVE-2019-19301siemensscalance_x-200irt_firmware+89
EPSS score
1.36%
A vulnerability has been identified in SCALANCE X200-4P IRT, SCALANCE X201-3P IRT, SCALANCE X201-3P IRT PRO, SCALANCE X202-2IRT, SCALANCE X202-2P IRT, SCALANCE X202-2P IRT PRO, SCALANCE X204-2, SCALANCE X204-2FM, SCALANCE X204-2LD, SCALANCE X204-2LD TS, SCALANCE X204-2TS, SCALANCE X204IRT, SCALANCE X204IRT PRO, SCALANCE X206-1, SCALANCE X206-1LD, SCALANCE X208, SCALANCE X208PRO, SCALANCE X212-2, SCALANCE X212-2LD, SCALANCE X216, SCALANCE X224, SCALANCE X302-7 EEC (230V, coated), SCALANCE X302-7 EEC (230V), SCALANCE X302-7 EEC (24V, coated), SCALANCE X302-7 EEC (24V), SCALANCE X302-7 EEC (2x 230V, coated), SCALANCE X302-7 EEC (2x 230V), SCALANCE X302-7 EEC (2x 24V, coated), SCALANCE X302-7 EEC (2x 24V), SCALANCE X304-2FE, SCALANCE X306-1LD FE, SCALANCE X307-2 EEC (230V, coated), SCALANCE X307-2 EEC (230V), SCALANCE X307-2 EEC (24V, coated), SCALANCE X307-2 EEC (24V), SCALANCE X307-2 EEC (2x 230V, coated), SCALANCE X307-2 EEC (2x 230V), SCALANCE X307-2 EEC (2x 24V, coated), SCALANCE X307-2 EEC (2x 24V), SCALANCE X307-3, SCALANCE X307-3, SCALANCE X307-3LD, SCALANCE X307-3LD, SCALANCE X308-2, SCALANCE X308-2, SCALANCE X308-2LD, SCALANCE X308-2LD, SCALANCE X308-2LH, SCALANCE X308-2LH, SCALANCE X308-2LH+, SCALANCE X308-2LH+, SCALANCE X308-2M, SCALANCE X308-2M, SCALANCE X308-2M PoE, SCALANCE X308-2M PoE, SCALANCE X308-2M TS, SCALANCE X308-2M TS, SCALANCE X310, SCALANCE X310, SCALANCE X310FE, SCALANCE X310FE, SCALANCE X320-1 FE, SCALANCE X320-1-2LD FE, SCALANCE X408-2, SCALANCE XF201-3P IRT, SCALANCE XF202-2P IRT, SCALANCE XF204, SCALANCE XF204-2, SCALANCE XF204-2BA IRT, SCALANCE XF204IRT, SCALANCE XF206-1, SCALANCE XF208, SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on front), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (230V, ports on rear), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on front), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M (24V, ports on rear), SCALANCE XR324-12M TS (24V), SCALANCE XR324-12M TS (24V), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on front), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (24V, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on front), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 100-240VAC/60-250VDC, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on front), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M EEC (2x 24V, ports on rear), SCALANCE XR324-4M PoE (230V, ports on front), SCALANCE XR324-4M PoE (230V, ports on rear), SCALANCE XR324-4M PoE (24V, ports on front), SCALANCE XR324-4M PoE (24V, ports on rear), SCALANCE XR324-4M PoE TS (24V, ports on front), SIMATIC CP 343-1 Advanced, SIMATIC CP 442-1 RNA, SIMATIC CP 443-1, SIMATIC CP 443-1, SIMATIC CP 443-1 Advanced, SIMATIC CP 443-1 RNA, SIMATIC RF180C, SIMATIC RF182C, SIPLUS NET CP 343-1 Advanced, SIPLUS NET CP 443-1, SIPLUS NET CP 443-1 Advanced, SIPLUS NET SCALANCE X308-2. The VxWorks-based Profinet TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
7.4CVE-2023-29054siemensscalance_x200-4p_irt_firmware+12
EPSS score
0.26%
A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT PRO (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2P IRT (All versions < V5.5.2), SCALANCE X202-2P IRT PRO (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT PRO (All versions < V5.5.2), SCALANCE XF201-3P IRT (All versions < V5.5.2), SCALANCE XF202-2P IRT (All versions < V5.5.2), SCALANCE XF204-2BA IRT (All versions < V5.5.2), SCALANCE XF204IRT (All versions < V5.5.2), SIPLUS NET SCALANCE X202-2P IRT (All versions < V5.5.2). The SSH server on affected devices is configured to offer weak ciphers by default. This could allow an unauthorized attacker in a man-in-the-middle position to read and modify any data passed over the connection between legitimate clients and the affected device.