Siemens Simatic S7 1500 CPU 1515 2 PN vulnerabilities, page 2

28 vulnerabilities

Known vulnerabilities in Siemens Simatic S7 1500 CPU 1515 2 PN, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

7.8CVE-2019-19281siemens agsimatic et 200sp open controller cpu 1515sp pc2 (incl. siplus variants)+16
EPSS score
1.68%
A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V2.5 and < V20.8), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 and < V2.8), SIMATIC S7-1500 Software Controller (All versions >= V2.5 and < V20.8). Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a Denial-of-Service condition. The vulnerability can be triggered if specially crafted UDP packets are sent to the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the device availability.
7.5CVE-2019-19300siemensdevelopment/evaluation kits for profinet io: ek-ertec 200+83
EPSS score
1.72%
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0), SIMATIC ET 200eco PN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0), SIMATIC ET 200eco PN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0), SIMATIC ET 200eco PN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0), SIMATIC ET 200eco PN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0), SIMATIC ET 200eco PN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0), SIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0), SIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0), SIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0), SIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0), SIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants), SIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC MICRO-DRIVE PDC, SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET 200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0), SIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0), SIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0), SIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0), SIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0), SIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0), SIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0), SIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0), SIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0), SIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0), SIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0), SIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0), SINAMICS S/G Control Unit w. PROFINET, SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0), SIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0), SIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0), SIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0), SIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0), SIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0), SIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0), SIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0). The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
9.3CVE-2026-25787siemenssimatic drive controller cpu 1504d tf+101
EPSS score
0.54%
Affected devices do not properly validate and sanitize Technology Object (TO) name rendered on the "Motion Control Diagnostics" page of the web interface. This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page. If a benign user with appropriate rights accesses the "Motion Control Diagnostics" parameters page, the malicious code would be executed in the scope of their web session.
7.2CVE-2026-25789siemenssimatic drive controller cpu 1504d tf+101
EPSS score
0.47%
Affected devices do not properly validate and sanitize filenames on the Firmware Update page. This could allow a remote attacker to social engineer the user into selecting the modified firmware file to be uploaded. This would result in malitcious JavaScript execution in the context of the authenticated user's session without requiring the file to be uploaded, potentially leading to session hijacking or credential theft.
9.3CVE-2026-25786siemenssimatic drive controller cpu 1504d tf+101
EPSS score
0.54%
Affected devices do not properly validate and sanitize PLC/station name rendered on the "communication" parameters page of the web interface. This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page. If a benign user with appropriate rights accesses the "communication" parameters page, the malicious code would be executed in the scope of their web session.
6.9CVE-2023-37482siemenssimatic drive controller cpu 1504d tf+91
EPSS score
0.51%
The login functionality of the web server in affected devices does not normalize the response times of login attempts. An unauthenticated remote attacker could exploit this side-channel information to distinguish between valid and invalid usernames.
7.5CVE-2023-46156siemenssimatic drive controller cpu 1504d tf+79
EPSS score
1.24%
Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a denial of service condition. A restart is needed to restore normal operations.
8.7CVE-2023-28831siemenssimatic braumat+116
EPSS score
1.13%
The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation. This could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate.