CVE-2024-46886siemenssimatic drive controller cpu 1504d tf+125
EPSS score0.40%
The web server of affected devices does not properly validate input that is used for a user redirection. This could allow an attacker to make the server redirect the legitimate user to an attacker-chosen URL. For a successful exploit, the legitimate user must actively click on an attacker-crafted link.CVE-2024-46887siemenssimatic drive controller cpu 1504d tf+86EPSS score0.56%
The web server of affected devices do not properly authenticate user request to the '/ClientArea/RuntimeInfoData.mwsl' endpoint. This could allow an unauthenticated remote attacker to gain knowledge about current actual and configured maximum cycle times as well as about configured maximum communication load.CVE-2019-10929siemenssimatic_cp_1626_firmware+25EPSS score0.98%
A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.CVE-2019-10943siemenssimatic drive controller family+16EPSS score0.95%
A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V20.8), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-1500 Software Controller (All versions >= V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC S7-PLCSIM Advanced (All versions >= V3.0). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device.CVE-2019-6568siemenssimatic_cp_1604_firmware+125EPSS score1.40%
The webserver of the affected devices contains a vulnerability that may lead to
a denial of service condition. An attacker may cause a denial of service
situation which leads to a restart of the webserver of the affected device.
The security vulnerability could be exploited by an attacker with network
access to the affected systems. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise availability of the device.CVE-2026-54429siemenssimatic s7-plcsim advancedEPSS score0.27%
A vulnerability has been identified in SIMATIC S7-PLCSIM Advanced (All versions). Affected devices do not properly handle high-volume multicast network traffic, which can exhaust available memory resources in the affected application. This could allow an unauthenticated attacker on the local network segment to cause a denial-of-service condition of the affected application. The affected application becomes inaccessible and requires a manual restart; no project data is lost. Successful exploitation requires a specific project configuration to be already active on the targeted instance.CVE-2026-25787siemenssimatic drive controller cpu 1504d tf+101EPSS score0.54%
Affected devices do not properly validate and sanitize Technology Object (TO) name rendered on the "Motion Control Diagnostics" page of the web interface. This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page.
If a benign user with appropriate rights accesses the "Motion Control Diagnostics" parameters page, the malicious code would be executed in the scope of their web session.CVE-2026-25789siemenssimatic drive controller cpu 1504d tf+101EPSS score0.47%
Affected devices do not properly validate and sanitize filenames on the Firmware Update page. This could allow a remote attacker to social engineer the user into selecting the modified firmware file to be uploaded. This would result in malitcious JavaScript execution in the context of the authenticated user's session without requiring the file to be uploaded, potentially leading to session hijacking or credential theft.CVE-2026-25786siemenssimatic drive controller cpu 1504d tf+101EPSS score0.54%
Affected devices do not properly validate and sanitize PLC/station name rendered on the "communication" parameters page of the web interface.
This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page.
If a benign user with appropriate rights accesses the "communication" parameters page, the malicious code would be executed in the scope of their web session.CVE-2023-37482siemenssimatic drive controller cpu 1504d tf+91EPSS score0.51%
The login functionality of the web server in affected devices does not normalize the response times of login attempts. An unauthenticated remote attacker could exploit this side-channel information to distinguish between valid and invalid usernames.CVE-2023-46156siemenssimatic drive controller cpu 1504d tf+79EPSS score1.24%
Affected devices improperly handle specially crafted packets sent to port 102/tcp.
This could allow an attacker to create a denial of service condition. A restart is needed to restore
normal operations.CVE-2023-28831siemenssimatic braumat+116EPSS score1.13%
The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation.