Siemens Simatic Wincc V8.0 vulnerabilities

9 vulnerabilities

Known vulnerabilities in Siemens Simatic Wincc V8.0, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.

8.8CVE-2026-59241siemenssimatic wincc v7.5+2
EPSS score
0.50%
A vulnerability has been identified in SIMATIC WinCC V7.5 (All versions), SIMATIC WinCC V8.0 (All versions < V8.0 Update 11), SIMATIC WinCC V8.1 (All versions < V8.1 Update 7). The affected application does not sufficiently restrict the permissions assigned to a database role. This could allow an authenticated remote attacker with database access to escalate privileges and execute arbitrary commands on the host system where SIMATIC WinCC is installed, potentially leading to a compromise of the system.
8.5CVE-2025-30033siemensautomation license manager v6.0+138
EPSS score
0.21%
The affected setup component is vulnerable to DLL hijacking. This could allow an attacker to execute arbitrary code when a legitimate user installs an application that uses the affected setup component.
8.2CVE-2024-30321siemenssimatic pcs 7 v9.1+5
EPSS score
0.51%
A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 23), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly handle certain requests to their web application, which may lead to the leak of privileged information. This could allow an unauthenticated remote attacker to retrieve information such as users and passwords.
9.4CVE-2024-35783siemenssimatic batch v9.1+10
EPSS score
0.61%
A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions < V2020 SP2 Update 5), SIMATIC Information Server 2022 (All versions < V2022 SP1 Update 2), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC06), SIMATIC Process Historian 2020 (All versions < V2020 SP2 Update 5), SIMATIC Process Historian 2022 (All versions < V2022 SP1 Update 2), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 3), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 18), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products run their DB server with elevated privileges which could allow an authenticated attacker to execute arbitrary OS commands with administrative privileges.
7.1CVE-2023-48364siemensopenpcs_7+14
EPSS score
0.27%
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call) communication protocol in the affected products do not properly handle certain malformed RPC messages. An attacker could use this vulnerability to cause a denial of service condition in the RPC server.
7.1CVE-2023-48363siemensopenpcs_7+14
EPSS score
0.27%
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call) communication protocol in the affected products do not properly handle certain unorganized RPC messages. An attacker could use this vulnerability to cause a denial of service condition in the RPC server.
8.2CVE-2023-46280siemenssecurity configuration tool (sct)+32
EPSS score
0.26%
A vulnerability has been identified in Security Configuration Tool (SCT) (All versions), SIMATIC Automation Tool (All versions < V5.0 SP2), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 Upd5), SIMATIC NET PC Software V16 (All versions < V16 Update 8), SIMATIC NET PC Software V17 (All versions), SIMATIC NET PC Software V18 (All versions < V18 SP1), SIMATIC NET PC Software V19 (All versions < V19 Update 2), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PDM V9.2 (All versions < V9.2 SP2 Upd3), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 Upd3), SIMATIC S7-PCT (All versions < V3.5 SP3 Update 6), SIMATIC STEP 7 V5 (All versions < V5.7 SP3), SIMATIC WinCC OA V3.17 (All versions), SIMATIC WinCC OA V3.18 (All versions < V3.18 P025), SIMATIC WinCC OA V3.19 (All versions < V3.19 P010), SIMATIC WinCC Runtime Advanced (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V16 (All versions < V16 Update 6), SIMATIC WinCC Runtime Professional V17 (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5), SINAMICS Startdrive (All versions < V19 SP1), SINEC NMS (All versions < V3.0), SINUMERIK ONE virtual (All versions < V6.23), SINUMERIK PLC Programming Tool (All versions < V3.3.12), TIA Portal Cloud Connector (All versions < V2.0), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 4), Totally Integrated Automation Portal (TIA Portal) V19 (All versions < V19 Update 2), SINEC NMS (All versions < V3.0 SP1). The affected applications contain an out of bounds read vulnerability. This could allow an attacker to cause a Blue Screen of Death (BSOD) crash of the underlying Windows kernel.
8.7CVE-2023-28831siemenssimatic braumat+116
EPSS score
1.13%
The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation. This could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate.
6.9CVE-2023-50821siemenssimatic pcs 7 v9.1+5
EPSS score
0.18%
A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC04), SIMATIC WinCC Runtime Professional V17 (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 1), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 16), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly validate the input provided in the login dialog box. An attacker could leverage this vulnerability to cause a persistent denial of service condition.