Trianglemicroworks vulnerabilities, page 2
25 vulnerabilities
Known vulnerabilities in Trianglemicroworks products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 7 products.
CVE-2023-39465triangle microworksscada data gateway+1
EPSS score0.76%
Triangle MicroWorks SCADA Data Gateway Use of Hard-coded Cryptograhic Key Information Disclosure Vulnerability. This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.
The specific flaw exists within the TmwCrypto class. The issue results from the usage of a hard-coded cryptograhic key and the usage of a hard-coded certificate. An attacker can leverage this vulnerability to disclose sensitive information. Was ZDI-CAN-20615.CVE-2023-39460triangle microworksscada data gateway+1EPSS score3.44%
Triangle MicroWorks SCADA Data Gateway Event Log Directory Traversal Arbitrary File Creation Vulnerability. This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the creation of event logs. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of root. Was ZDI-CAN-20534.CVE-2023-39466triangle microworksscada data gateway+1EPSS score1.01%
Triangle MicroWorks SCADA Data Gateway get_config Missing Authentication Information Disclosure Vulnerability. This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.
The specific flaw exists within the get_config endpoint. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to disclose sensitive information. Was ZDI-CAN-20797.CVE-2023-39464triangle microworksscada data gateway+1EPSS score1.99%
Triangle MicroWorks SCADA Data Gateway GTWWebMonitorService Unquoted Search Path Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root. Was ZDI-CAN-20538.CVE-2023-39461triangle microworksscada data gateway+1EPSS score1.30%
Triangle MicroWorks SCADA Data Gateway Event Log Improper Output Neutralization For Logs Arbitrary File Write Vulnerability. This vulnerability allows remote attackers to write arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the handling of event logs. The issue results from improper sanitization of log output. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of root. Was ZDI-CAN-20535.