CVE-2023-29464: rockwell automation factorytalk linx Improper Input Validation
Vulnerability summary
CVE-2023-29464 is a critical (CVSS 9.1) Improper Input Validation vulnerability in rockwell automation factorytalk linx. EPSS estimates a 14.97% chance of exploitation in the next 30 days, higher than 96.6% of scored vulnerabilities.
Timeline
- 13-10-2023PublishedVulnerability first disclosed.
- 17-09-2024Last modifiedVulnerability information updated.
Description
FactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from memory via crafted malicious packets. Sending a size larger than the buffer size results in leakage of data from memory resulting in an information disclosure. If the size is large enough, it causes communications over the common industrial protocol to become unresponsive to any type of packet, resulting in a denial-of-service to FactoryTalk Linx over the common industrial protocol.
CVSS metrics
2 scores · 2 sources · 1 version- CVE.orgCNA8.2HighCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:HDiffers
EPSS trend
Probability
14.97%
Chance of exploitation in the next 30 days
Percentile
97%
Versus all other CVEs
30-day change
+5.37 pp
From 9.60% on 20-09-2026
Known exploited
Compare KEV catalogsNot in any of the 3 tracked catalogs.
Public exploits
0 foundNo public exploits indexed.
Weaknesses
CWE · root cause- CWE-20Improper Input ValidationThe product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.
- CWE-787Out-of-bounds WriteThe product writes data past the end, or before the beginning, of the intended buffer.
Affected systems
Rockwell automation1 product
- factorytalk linx6.20 | 6.30
Rockwellautomation1 product
- factorytalk_linx6.20 | 6.30
2 vendors · 2 products
References
1 links- rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1141040Permissions RequiredVendor Advisory