CVE-2025-7693: rockwell automation plc - micro850 l50e Improper Input Validation
Vulnerability summary
CVE-2025-7693 is a critical (CVSS 9.3) Improper Input Validation vulnerability in rockwell automation plc - micro850 l50e. EPSS estimates a 0.37% chance of exploitation in the next 30 days, higher than 29.2% of scored vulnerabilities.
Timeline
- 18-08-2025PublishedVulnerability first disclosed.
- 18-08-2025Last modifiedVulnerability information updated.
Description
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
CVSS metrics
2 scores · 2 sources · 1 version- NVDNIST9.3CriticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS trend
Probability
0.37%
Chance of exploitation in the next 30 days
Percentile
29%
Versus all other CVEs
30-day change
0.00 pp
From 0.37% on 22-09-2026
Known exploited
Compare KEV catalogsNot in any of the 3 tracked catalogs.
Public exploits
0 foundNo public exploits indexed.
Weaknesses
CWE · root causeAffected systems
Rockwell automation1 product
- plc - micro850 l50eV20.011 - V22.011
1 vendor · 1 product