Hitachi Energy vulnerabilities, page 2
115 vulnerabilities
Known vulnerabilities in Hitachi Energy products, newest first, with CVSS severity, EPSS, KEV listings and ransomware use, across 60 products.
CVE-2025-1037hitachi energytropos 4th gen
EPSS score0.15%
By making minor configuration changes to the TropOS 4th Gen device, an authenticated user with the ability to run user level shell commands can enable access via secure shell (SSH) to an unrestricted root shell. This is possible through abuse of a particular set of scripts and executables that allow for certain commands to be run as root from an unprivileged context.CVE-2025-1445hitachi energyrtu500EPSS score0.34%
A vulnerability exists in RTU IEC 61850 client and server functionality that could impact the availability if renegotiation of an open IEC61850 TLS connection takes place in specific timing situations, when IEC61850 communication is active.
Precondition is that IEC61850 as client or server are configured using TLS on RTU500 device. It affects the CMU the IEC61850 stack is configured on.CVE-2025-1038hitachi energytropos 4th genEPSS score0.32%
The “Diagnostics Tools” page of the web-based configuration utility does not properly validate user-controlled input, allowing an authenticated user with high privileges to inject commands into the command shell of the TropOS 4th Gen device. The injected commands can be exploited to execute several set-uid (SUID) applications to ultimately gain root access to the TropOS device.CVE-2025-39201hitachi energymicroscada x sys600+1EPSS score0.13%
A vulnerability exists in MicroSCADA X SYS600 product. If exploited this could allow a local unauthenticated attacker to tamper a system file, making denial of Notify service.CVE-2025-39204hitachi energymicroscada x sys600+1EPSS score0.36%
A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface can be malformed, so returning data can leak unauthorized information to the user.CVE-2025-39203hitachi energymicroscada x sys600+1EPSS score0.22%
A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.CVE-2025-39205hitachi energymicroscada x sys600+1EPSS score0.20%
A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol allows remote Man-in-the-Middle attack due to missing proper validation.CVE-2025-39202hitachi energymicroscada x sys600+1EPSS score0.23%
A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption.CVE-2025-7740hitachi energysuprosEPSS score0.17%
Default credentials vulnerability exists in SuprOS
product. If exploited, this could allow an authenticated
local attacker to use an admin account created during
product deployment.CVE-2025-27632hitachi energytrmtrackerEPSS score0.25%
A Host Header Injection vulnerability in TRMTracker application may allow an attacker by modifying the host header value in an HTTP request to leverage multiple attack vectors, including defacing the site content through web-cache poisoning.CVE-2025-27633hitachi energytrmtrackerEPSS score0.25%
The TRMTracker web application is vulnerable to reflected Cross-site scripting attack. The application allows client-side code injection that might be used to compromise the confidentiality and integrity of the system.CVE-2025-27631hitachi energytrmtrackerEPSS score0.27%
The TRMTracker web application is vulnerable to LDAP injection attack potentially allowing an attacker to inject code into a query and execute remote commands that can read and update data on the website.CVE-2025-10217hitachi energyasset suiteEPSS score0.29%
A vulnerability exists in Asset Suite for an authenticated user to manipulate the content of performance related log data or to inject crafted data in logfile for potentially carrying out further malicious attacks. Performance logging is typically enabled for troubleshooting purposes while resolving application performance related issues.CVE-2022-2513hitachi energy650 connectivity package+11EPSS score0.15%
A vulnerability exists in the Intelligent Electronic Device (IED) Connectivity Package (ConnPack) credential storage function in Hitachi Energy’s PCM600 product included in the versions listed below, where IEDs credentials are stored in a cleartext format in the PCM600 database and logs files. An attacker having get access to the exported backup file can exploit the vulnerability and obtain user credentials of the IEDs. Additionally, an attacker with administrator access to the PCM600 host machine can obtain other user credentials by analyzing database log files. The credentials may be used to perform unauthorized modifications such as loading incorrect configurations, reboot the IEDs or cause a denial-of-service on the IEDs.CVE-2022-2277hitachi energymicroscada x sys600+1EPSS score0.77%
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*CVE-2022-2502hitachi energyrtu500 series+1EPSS score0.65%
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.CVE-2022-2081hitachi energyrtu500 series cmu firmware+4EPSS score0.64%
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.CVE-2022-2155hitachi energylumada apm+1EPSS score0.37%
A vulnerability exists in the affected versions of Lumada APM’s User Asset Group feature
due to a flaw in access control mechanism implementation on the “Limited Engineer” role, granting it access to the embedded Power BI reports
feature. An attacker that manages to exploit the vulnerability on a customer’s Lumada APM could access unauthorized information by gaining
unauthorized access to any Power BI reports installed by the customer.
Furthermore, the vulnerability enables an attacker to manipulate asset issue comments on assets, which should not be available to the attacker.
Affected versions
* Lumada APM on-premises version 6.0.0.0 - 6.4.0.*
List of CPEs:
* cpe:2.3:a:hitachienergy:lumada_apm:6.0.0.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:lumada_apm:6.1.0.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:lumada_apm:6.2.0.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:lumada_apm:6.3.0.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:lumada_apm:6.4.0.0:*:*:*:*:*:*:*CVE-2022-1778hitachi energymicroscada x sys600+1EPSS score0.48%
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*CVE-2022-4608hitachi energyrtu500 series+1EPSS score0.71%
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.