Siemens Sinamics S120 vulnerabilities
9 vulnerabilities
Known vulnerabilities in Siemens Sinamics S120, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.
CVE-2013-6920siemenssinamics_g110+13
EPSS score3.23%
Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23.CVE-2022-47375siemenssimatic_pc-station_plus_firmware+9EPSS score0.72%
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle long file names correctly.
This could allow an attacker to create a buffer overflow and create a denial of service condition for the device.CVE-2022-47374siemenssimatic_pc-station_plus_firmware+9EPSS score0.72%
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly.
This could allow an attacker to exhaust system resources and create a denial of service condition for the device.CVE-2017-2681siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+174EPSS score0.91%
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.CVE-2017-2680siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+200EPSS score1.15%
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.CVE-2017-12741siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+118EPSS score3.31%
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.CVE-2019-10936siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+139EPSS score2.07%
Affected devices improperly handle large amounts of specially crafted UDP packets.
This could allow an unauthenticated remote attacker to trigger a denial of service condition.CVE-2019-10923siemenscp1604_firmware+110EPSS score1.40%
An attacker with network access to an affected product may cause a denial of service condition by breaking the real-time synchronization (IRT) of the affected installation.CVE-2019-6568siemenssimatic_cp_1604_firmware+125EPSS score1.40%
The webserver of the affected devices contains a vulnerability that may lead to
a denial of service condition. An attacker may cause a denial of service
situation which leads to a restart of the webserver of the affected device.
The security vulnerability could be exploited by an attacker with network
access to the affected systems. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise availability of the device.