Wago 750 363 vulnerabilities
4 vulnerabilities
Known vulnerabilities in Wago 750 363, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.
CVE-2018-16210wago750-352_firmware+13
EPSS score0.95%
WAGO 750-88X and WAGO 750-89X Ethernet Controller devices, versions 01.09.18(13) and before, have XSS in the SNMP configuration via the webserv/cplcfg/snmp.ssi SNMP_DESC or SNMP_LOC_SNMP_CONT field.CVE-2021-34578wago750-362_firmware+12EPSS score0.96%
This vulnerability allows an attacker who has access to the WBM to read and write settings-parameters of the device by sending specifically constructed requests without authentication on multiple WAGO PLCs in firmware versions up to FW07.CVE-2020-12506wago750-362_firmware+8EPSS score1.45%
Improper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW03 allows an attacker to change the settings of the devices by sending specifically constructed requests without authentication This issue affects: WAGO 750-362, WAGO 750-363, WAGO 750-823, WAGO 750-832/xxx-xxx, WAGO 750-862, WAGO 750-891, WAGO 750-890/xxx-xxx in versions FW03 and prior versions.CVE-2023-1150wago750-332+24EPSS score0.93%
Uncontrolled resource consumption in Series WAGO 750-3x/-8x products may allow an unauthenticated remote attacker to DoS the MODBUS server with specially crafted packets.