CVE-2019-10918: siemens ag simatic pcs 7 v8.0 and earlier Exposed Dangerous Method or Function
Vulnerability summary
CVE-2019-10918 is a high (CVSS 9.0) Exposed Dangerous Method or Function vulnerability in siemens ag simatic pcs 7 v8.0 and earlier. EPSS estimates a 1.93% chance of exploitation in the next 30 days, higher than 79.6% of scored vulnerabilities.
Timeline
- 14-05-2019PublishedVulnerability first disclosed.
- 04-08-2024Last modifiedVulnerability information updated.
Description
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVSS metrics
2 scores · 1 source · 2 versionsEPSS trend
Probability
1.93%
Chance of exploitation in the next 30 days
Percentile
80%
Versus all other CVEs
30-day change
0.00 pp
From 1.93% on 18-09-2026
Known exploited
Compare KEV catalogsNot in any of the 3 tracked catalogs.
Public exploits
0 foundNo public exploits indexed.
Weaknesses
CWE · root causeAffected systems
Siemens ag14 products
- simatic pcs 7 v8.0 and earlierAll versions (No fix recorded)
- simatic pcs 7 v8.1All versions < V8.1 with WinCC V7.3 Upd 19
- simatic pcs 7 v8.2All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11
- simatic pcs 7 v9.0All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11
- simatic wincc runtime professional v13All versions (No fix recorded)
Siemens3 products
- simatic_pcs_7≤ 8.0 | 8.1 | 8.2 | 9.0
- simatic_wincc≤ 7.2 | 7.3 | 7.4 | 7.5
- simatic_wincc_\(tia_portal\)13.0 | 14.0 | 15.0
2 vendors · 17 products
References
2 links- www.us-cert.gov/ics/advisories/ICSA-19-134-08X Refsource MISCThird Party AdvisoryUS Government Resource