CVE-2019-10935: siemens ag simatic pcs 7 v8.0 and earlier
Vulnerability summary
CVE-2019-10935 is a high (CVSS 7.2) vulnerability in siemens ag simatic pcs 7 v8.0 and earlier. EPSS estimates a 1.30% chance of exploitation in the next 30 days, higher than 69.9% of scored vulnerabilities.
Timeline
- 11-07-2019PublishedVulnerability first disclosed.
- 04-08-2024Last modifiedVulnerability information updated.
Description
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
CVSS metrics
2 scores · 1 source · 2 versionsEPSS trend
Probability
1.30%
Chance of exploitation in the next 30 days
Percentile
70%
Versus all other CVEs
30-day change
0.00 pp
From 1.30% on 18-09-2026
Known exploited
Compare KEV catalogsNot in any of the 3 tracked catalogs.
Public exploits
0 foundNo public exploits indexed.
Weaknesses
CWE · root causeAffected systems
Siemens ag14 products
- simatic pcs 7 v8.0 and earlierAll versions (No fix recorded)
- simatic pcs 7 v8.1All versions < V8.1 with WinCC V7.3 Upd 19
- simatic pcs 7 v8.2All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11
- simatic pcs 7 v9.0All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11
- simatic wincc professional (tia portal v13)All versions (No fix recorded)
Siemens3 products
- simatic_pcs_78.0 | 8.1 | 8.2 | 9.0
- simatic_wincc≤ 7.2 | 7.3 | 7.3:update_1 | 7.3:update_10 | 7.3:update_11 | 7.3:update_13 | 7.3:update_4 | 7.4 | 7.4:sp1 | 7.4:update_1 | 7.5 | 13 | 13:sp2 | 14 | 14:sp1 | 15
- simatic_wincc_runtime14 | 14:sp1 | 15 | 15:update_4 | 15.1 | 15.1:update_1 | 13 | 13:sp1 | 13:sp2
2 vendors · 17 products