8.8

CVE-2021-31888: siemens apogee mbc (ppc) (bacnet) Improper Null Termination

CVSS: 8.8v3.1HighModified
Published 09-11-2021Last modified 03-08-2024

Vulnerability summary

CVE-2021-31888 is a high (CVSS 8.8) Improper Null Termination vulnerability in siemens apogee mbc (ppc) (bacnet). EPSS estimates a 2.45% chance of exploitation in the next 30 days, higher than 84.1% of scored vulnerabilities.

Overall risk
36/100
0100
Medium · default modelHow is this calculated?
CVSS score
8.8/10
010
High · v3.1 (NVD)
EPSS score
2.45%
0%100%
Low · 0.00 pp in 30 days
KEVNot listedIn no KEV catalog
RansomwareNone recordedNo known use recorded
Public exploits0No public exploits recorded

Timeline

  1. 09-11-2021
    PublishedVulnerability first disclosed.
  2. 03-08-2024
    Last modifiedVulnerability information updated.

Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). FTP server does not properly validate the length of the “MKD/XMKD” command, leading to stack-based buffer overflows. This may result in Denial-of-Service conditions and Remote Code Execution. (FSMD-2021-0018)

CVSS metrics

2 scores · 1 source · 2 versions

EPSS trend

Probability

2.45%

Chance of exploitation in the next 30 days

Percentile

84%

Versus all other CVEs

30-day change

0.00 pp

From 2.45% on 19-09-2026

19-09-202619-10-2026
EPSS score
2.45%

Known exploited

Compare KEV catalogs

Not in any of the 3 tracked catalogs.

Public exploits

0 found

No public exploits indexed.

Weaknesses

CWE · root cause

Affected systems

Siemens30 products

1 vendor · 30 products

References

2 links