CVE-2022-40202: delta electronics infrasuite device master
Vulnerability summary
CVE-2022-40202 is a critical (CVSS 9.8) vulnerability in delta electronics infrasuite device master. EPSS estimates a 1.40% chance of exploitation in the next 30 days, higher than 72.3% of scored vulnerabilities.
Timeline
- 31-10-2022PublishedVulnerability first disclosed.
- 16-04-2025Last modifiedVulnerability information updated.
Description
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
CVSS metrics
2 scores · 2 sources · 1 version- NVDNIST9.8CriticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS trend
Probability
1.40%
Chance of exploitation in the next 30 days
Percentile
72%
Versus all other CVEs
30-day change
+0.06 pp
From 1.34% on 21-09-2026
Known exploited
Compare KEV catalogsNot in any of the 3 tracked catalogs.
Public exploits
0 foundNo public exploits indexed.
Weaknesses
CWE · root causeAffected systems
Delta electronics1 product
- infrasuite device master≤ 00.00.01a
Deltaww1 product
- infrasuite_device_master< 00.00.02a
2 vendors · 2 products
References
1 links- www.cisa.gov/uscert/ics/advisories/icsa-22-298-07Government ResourcePatchThird Party AdvisoryUS Government Resource