Siemens Simatic S7 400 Pn/Dp V6 And Below CPU Family (Incl. Siplus Variants) vulnerabilities
7 vulnerabilities
Known vulnerabilities in Siemens Simatic S7 400 Pn/Dp V6 And Below CPU Family (Incl. Siplus Variants), newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.
CVE-2018-16556siemenssimatic_s7-400_firmware+23
EPSS score1.54%
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via
PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected
devices to go into defect mode. Manual reboot is required to resume normal
operation.
Successful exploitation requires an attacker to be able to send specially
crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi
Point Interfaces (MPI). No user interaction and no user privileges are
required to exploit the security vulnerability. The vulnerability could allow
causing a denial of service condition of the core functionality of the CPU,
compromising the availability of the system.CVE-2018-16557siemenssimatic_s7-400_firmware+23EPSS score0.82%
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface
via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service
condition on affected devices. Flashing with a firmware image may be required
to recover the CPU.
Successful exploitation requires an attacker to have network access to port
102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or
Multi Point Interfaces (MPI) to the device. No user interaction is required.
If no access protection is configured, no privileges are required to exploit
the security vulnerability. The vulnerability could allow causing a
denial of service condition of the core functionality of the CPU,
compromising the availability of the system.CVE-2017-12741siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+118EPSS score3.31%
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.CVE-2019-13940siemenss7-1200_cpu_1211c_firmware+39EPSS score1.70%
A vulnerability has been identified in SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.1), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.X.17), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX 2010 (All versions), SIMATIC WinAC RTX F 2010 (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17). Affected devices contain a vulnerability that could cause a denial of service condition of the web server
by sending specially crafted HTTP requests to ports 80/tcp and 443/tcp.
Beyond the web service, no other functions or interfaces are affected by the denial of service condition.CVE-2019-10936siemensdevelopment/evaluation kits for profinet io: dk standard ethernet controller+139EPSS score2.07%
Affected devices improperly handle large amounts of specially crafted UDP packets.
This could allow an unauthenticated remote attacker to trigger a denial of service condition.CVE-2019-10923siemenscp1604_firmware+110EPSS score1.40%
An attacker with network access to an affected product may cause a denial of service condition by breaking the real-time synchronization (IRT) of the affected installation.CVE-2019-6568siemenssimatic_cp_1604_firmware+125EPSS score1.40%
The webserver of the affected devices contains a vulnerability that may lead to
a denial of service condition. An attacker may cause a denial of service
situation which leads to a restart of the webserver of the affected device.
The security vulnerability could be exploited by an attacker with network
access to the affected systems. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise availability of the device.