7.8

CVE-2018-16556: siemens simatic_s7-400_firmware Improper Input Validation

CVSS: 7.8v2.0HighModified
Published 13-12-2018Last modified 05-08-2024

Vulnerability summary

CVE-2018-16556 is a high (CVSS 7.8) Improper Input Validation vulnerability in siemens simatic_s7-400_firmware. EPSS estimates a 1.54% chance of exploitation in the next 30 days, higher than 74.5% of scored vulnerabilities.

Overall risk
32/100
0100
Medium · default modelHow is this calculated?
CVSS score
7.8/10
010
High · v2.0 (NVD)
EPSS score
1.54%
0%100%
Low · 0.00 pp in 30 days
KEVNot listedIn no KEV catalog
RansomwareNone recordedNo known use recorded
Public exploits0No public exploits recorded

Timeline

  1. 13-12-2018
    PublishedVulnerability first disclosed.
  2. 05-08-2024
    Last modifiedVulnerability information updated.

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

CVSS metrics

3 scores · 2 sources · 2 versions

EPSS trend

Probability

1.54%

Chance of exploitation in the next 30 days

Percentile

75%

Versus all other CVEs

30-day change

0.00 pp

From 1.54% on 18-09-2026

18-09-202618-10-2026
EPSS score
1.54%

Known exploited

Compare KEV catalogs

Not in any of the 3 tracked catalogs.

Public exploits

0 found

No public exploits indexed.

Weaknesses

CWE · root cause

Affected systems

Siemens24 products

1 vendor · 24 products

References

1 links