Siemens Simatic Wincc vulnerabilities, page 2
31 vulnerabilities
Known vulnerabilities in Siemens Simatic Wincc, newest first, with CVSS severity, EPSS, KEV listings, ransomware use and the affected versions.
CVE-2019-19282siemensopenpcs_7+27
EPSS score1.34%
A vulnerability has been identified in OpenPCS 7 V8.1 (All versions), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd3), SIMATIC BATCH V8.1 (All versions), SIMATIC BATCH V8.2 (All versions < V8.2 Upd12), SIMATIC BATCH V9.0 (All versions < V9.0 SP1 Upd5), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC NET PC Software V16 (All versions < V16 Update 1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd4), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 10), SIMATIC WinCC (TIA Portal) V15.1 (All versions < V15.1 Update 5), SIMATIC WinCC (TIA Portal) V16 (All versions < V16 Update 1), SIMATIC WinCC V7.3 (All versions), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 1). Through specially crafted messages, when encrypted communication is enabled, an attacker with network access could use the vulnerability to compromise the availability of the system by causing a Denial-of-Service condition.
Successful exploitation requires no system privileges and no user interaction.CVE-2019-10929siemenssimatic_cp_1626_firmware+25EPSS score0.98%
A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.CVE-2019-10916siemens agsimatic pcs 7 v8.0 and earlier+16EPSS score1.54%
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file. The vulnerability does impact the confidentiality, integrity, and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.CVE-2019-10918siemens agsimatic pcs 7 v8.0 and earlier+16EPSS score1.93%
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.CVE-2019-10917siemens agsimatic pcs 7 v8.0 and earlier+16EPSS score0.27%
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with local access to the project file could cause a Denial-of-Service condition on the affected product while the project file is loaded. Successful exploitation requires access to the project file. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.CVE-2019-10922siemens agsimatic pcs 7 v8.0 and earlier+5EPSS score2.64%
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 and newer (All versions). An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.CVE-2019-10935siemens agsimatic pcs 7 v8.0 and earlier+16EPSS score1.30%
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.CVE-2023-48364siemensopenpcs_7+14EPSS score0.27%
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call) communication protocol in the affected products do not properly handle certain malformed RPC messages. An attacker could use this vulnerability to cause a denial of service condition in the RPC server.CVE-2023-48363siemensopenpcs_7+14EPSS score0.27%
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call)
communication protocol in the affected products do not
properly handle certain unorganized RPC messages. An
attacker could use this vulnerability to cause a denial of service
condition in the RPC server.CVE-2023-28829siemenssimatic_net_pc_software+8EPSS score0.29%
A vulnerability has been identified in SIMATIC NET PC Software V14 (All versions), SIMATIC NET PC Software V15 (All versions), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions), SIMATIC WinCC (All versions < V8.0), SINAUT Software ST7sc (All versions). Before SIMATIC WinCC V8, legacy OPC services (OPC DA (Data Access), OPC HDA (Historical Data Access), and OPC AE (Alarms & Events)) were used per default. These
services were designed on top of the Windows ActiveX and DCOM mechanisms and do not implement state-of-the-art security mechanisms for authentication and encryption of contents.CVE-2023-30897siemenssimatic_wincc+1EPSS score0.21%
A vulnerability has been identified in SIMATIC WinCC (All versions < V7.5.2.13). Affected applications fail to set proper access rights for their installation folder if a non-default installation path was chosen during installation.
This could allow an authenticated local attacker to inject arbitrary code and escalate privileges.